Notifications
You must be signed in to change notification settings - Fork 68
Open
Description
I can see this section from 90.1-2019:
but I don't think I'm finding the relevant code in os stds here. I did find the relevant code under 2013 subclass though:
Lines 10 to 40 in 4299746
def plant_loop_prm_baseline_condenser_water_temperatures(plant_loop, design_oat_wb_c) | |
design_oat_wb_f = OpenStudio.convert(design_oat_wb_c, 'C', 'F').get | |
# G3.1.3.11 - CW supply temp shall be evaluated at 0.4% evaporative design OATwb | |
# per the formulat approach_F = 25.72 - (0.24 * OATwb_F) | |
# 55F <= OATwb <= 90F | |
# Design range = 10F. | |
range_r = 10 | |
# Limit the OATwb | |
if design_oat_wb_f < 55 | |
design_oat_wb_f = 55 | |
OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.PlantLoop', "For #{plant_loop.name}, a design OATwb of 55F will be used for sizing the cooling towers because the actual design value is below the limit in G3.1.3.11.") | |
elsif design_oat_wb_f > 90 | |
design_oat_wb_f = 90 | |
OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.PlantLoop', "For #{plant_loop.name}, a design OATwb of 90F will be used for sizing the cooling towers because the actual design value is above the limit in G3.1.3.11.") | |
end | |
# Calculate the approach | |
approach_r = 25.72 - (0.24 * design_oat_wb_f) | |
# Calculate the leaving CW temp | |
leaving_cw_t_f = design_oat_wb_f + approach_r | |
# Convert to SI units | |
leaving_cw_t_c = OpenStudio.convert(leaving_cw_t_f, 'F', 'C').get | |
approach_k = OpenStudio.convert(approach_r, 'R', 'K').get | |
range_k = OpenStudio.convert(range_r, 'R', 'K').get | |
return [leaving_cw_t_c, approach_k, range_k] | |
end |
so, I'm assuming the same subclass should be available under 90.1-2019? or if it is unavailable in 2019, will it crawl back to find the method from 2013?
Metadata
Metadata
Assignees
Labels
No labels