Example Modbus TCP Server
This example shows how to configure a Modbus TCP server.
Written by FACTS Engineering
Copyright (c) 2023 FACTS Engineering, LLC
Licensed under the MIT license.
"""
import board
import busio
import digitalio
import p1am_200_helpers as helpers # For P1AM-ETH
from adafruit_wiznet5k.adafruit_wiznet5k import WIZNET5K
import adafruit_wiznet5k.adafruit_wiznet5k_socket as socket
from uModBus.tcp import TCPServer
led = digitalio.DigitalInOut(board.LED)
led.switch_to_output()
switch = digitalio.DigitalInOut(board.SWITCH)
# For P1AM-ETH
eth = helpers.get_ethernet(False) # DHCP False
# For generic ethernet
# cs = digitalio.DigitalInOut(board.D5)
# spi_bus = busio.SPI(board.SCK, MOSI=board.MOSI, MISO=board.MISO)
# eth = WIZNET5K(spi_bus, cs, is_dhcp=False)
IP_ADDRESS = (192, 168, 1, 177)
SUBNET_MASK = (255, 255, 248, 0)
GATEWAY_ADDRESS = (192, 168, 0, 1)
DNS_SERVER = (8, 8, 8, 8)
eth.ifconfig = (IP_ADDRESS, SUBNET_MASK, GATEWAY_ADDRESS, DNS_SERVER)
socket.set_interface(eth)
server_ip = eth.pretty_ip(eth.ip_address)
mb_server = TCPServer(
socket,
server_ip,
number_coils=0x20,
number_input_registers=0xFF,
number_discrete_inputs=0x10,
number_holding_registers=10,
)
mb_server.input_registers[0:] = list(range(0xFF)) # set input registers 0-255 to 0-255
mb_server.discrete_inputs[5] = True
mb_server.holding_registers.signed[1] = True # set holding register 1 to use 16-bit signed values
count = 0
while True:
try:
mb_server.poll(timeout=.1) # Regularly poll the modbus server to handle incoming requests
except RuntimeError as e:
pass # Ignore errors in case the client disconnects mid-poll
mb_server.discrete_inputs[0] = switch.value # set discrete input 0 to switch value
mb_server.holding_registers[0] = count # set holding register 0 to count value
mb_server.holding_registers[1] = -count # set holding register 1 to count value
led.value = mb_server.coils[0] # set led to output value
count += 1
if count > 32767:
count = 0 # reset count