I've got a Techem Ultra S3 (which is basically a rebranded Sharky 775) heat meter. For some reason the negative values show up prefixed with F. Is this expected?
Here for example we should have a negative power of 99 watts:
<DataRecord id="4">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Power (W)</Unit>
<Value>F0000099</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
This didn't happen previously on my old system, but unfortunately that one crashed, so I can't really go back and see which version of libmbus I was running there.
$ mbus-tcp-request-data -d 192.168.99.15 10001 7
[2021-12-22 08:56:00Z] SEND (005): 10 5B 07 62 16
[2021-12-22 08:56:01Z] RECV (110): 68 68 68 68 08 07 72 45 11 06 48 68 50 40 04 8C 00 00 00 0C 06 26 25 10 00 8C 10 06 00 00 00 00 8C 20 13 43 55 64 08 0C 13 56 13 30 36 0C 2B 99 00 00 F0 0B 3B 71 09 00 0A 5A 20 03 0A 5E 21 03 0A 62 00 F0 0A 27 66 29 04 6D 2A 0C B6 2C 4C 06 85 14 09 00 4C 13 82 71 73 28 CC 10 06 00 00 00 00 CC 20 13 11 95 61 05 42 6C 9F 2C EC 16
mbus_frame_print: Dumping M-Bus frame [type 4, 110 bytes]: 68 68 68 68 08 07 72 45 11 06 48 68 50 40 04 8C 00 00 00 0C 06 26 25 10 00 8C 10 06 00 00 00 00 8C 20 13 43 55 64 08 0C 13 56 13 30 36 0C 2B 99 00 00 F0 0B 3B 71 09 00 0A 5A 20 03 0A 5E 21 03 0A 62 00 F0 0A 27 66 29 04 6D 2A 0C B6 2C 4C 06 85 14 09 00 4C 13 82 71 73 28 CC 10 06 00 00 00 00 CC 20 13 11 95 61 05 42 6C 9F 2C EC 16
<?xml version="1.0" encoding="ISO-8859-1"?>
<MBusData>
<SlaveInformation>
<Id>48061145</Id>
<Manufacturer>TCH</Manufacturer>
<Version>64</Version>
<ProductName></ProductName>
<Medium>Heat: Outlet</Medium>
<AccessNumber>140</AccessNumber>
<Status>00</Status>
<Signature>0000</Signature>
</SlaveInformation>
<DataRecord id="0">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Energy (kWh)</Unit>
<Value>102526</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="1">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Tariff>1</Tariff>
<Device>0</Device>
<Unit>Energy (kWh)</Unit>
<Value>0</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="2">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Tariff>2</Tariff>
<Device>0</Device>
<Unit>Volume (m m^3)</Unit>
<Value>8645543</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="3">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Volume (m m^3)</Unit>
<Value>36301356</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="4">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Power (W)</Unit>
<Value>F0000099</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="5">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Volume flow (m m^3/h)</Unit>
<Value>971</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="6">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Flow temperature (1e-1 deg C)</Unit>
<Value>320</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="7">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Return temperature (1e-1 deg C)</Unit>
<Value>321</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="8">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Temperature Difference (1e-1 deg C)</Unit>
<Value>F000</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="9">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Operating time (days)</Unit>
<Value>2966</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="10">
<Function>Instantaneous value</Function>
<StorageNumber>0</StorageNumber>
<Unit>Time Point (time & date)</Unit>
<Value>2021-12-22T12:42:00</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="11">
<Function>Instantaneous value</Function>
<StorageNumber>1</StorageNumber>
<Unit>Energy (kWh)</Unit>
<Value>91485</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="12">
<Function>Instantaneous value</Function>
<StorageNumber>1</StorageNumber>
<Unit>Volume (m m^3)</Unit>
<Value>28737182</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="13">
<Function>Instantaneous value</Function>
<StorageNumber>1</StorageNumber>
<Tariff>1</Tariff>
<Device>0</Device>
<Unit>Energy (kWh)</Unit>
<Value>0</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="14">
<Function>Instantaneous value</Function>
<StorageNumber>1</StorageNumber>
<Tariff>2</Tariff>
<Device>0</Device>
<Unit>Volume (m m^3)</Unit>
<Value>5619511</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
<DataRecord id="15">
<Function>Instantaneous value</Function>
<StorageNumber>1</StorageNumber>
<Unit>Time Point (date)</Unit>
<Value>2020-12-31</Value>
<Timestamp>2021-12-22T08:56:01Z</Timestamp>
</DataRecord>
</MBusData>